Tower 3 Specification

Overall Size Approx. 114,700m2 NLA (Office Floors)
No. of office floor 40 floors (5th & 6th, 8th to 38th, 40th to 46th)
Typical Floor Area Approx. 2,800m2 NLA
Core to window depth Approx. 15.5m (N) / 14.3m (E) / 15.5m (S) / 14.0m (W)
Finished Floor-to-Ceiling Height Approx. 2,800mm
Raised Floor Approx. 180mm from top of slab to top of raised floor
Planning grid 1,500mm
Floor Loading Live Load = 3.5 kN/m2 ; Partitions = 1.0 kN/m2
Curtain Wall Unitised aluminium system with double glazed low E-solar tinted or single thermal toughened glass
Total no. of carparks Approx. 354 lots for tenants
Toilets Male and Female, 1 Executive Toilet with shower combined with a Handicapped Toilet per floor
Pantry Provision for tenant’s pantry exhaust connection to central pantry exhaust riser on every floor
Air-Conditioning 24-hour chilled water supply available from District Cooling System with two AHUs per floor Estimated cooling load is approx. 420 kWr
Two DCS chilled water tap-off points have been provided for each floor in conjunction with two supplementary chilled water tap off points which are backup by air-cooled chillers with emergency power supply for 20% of estimated cooling load
Two sets of spare chilled water riser pipes have been provided on each floor, subject to availability
Space available for 6 nos tenants’ own air-cooled chillers system, subject to availability
Security System 24-hour CCTV monitoring at all main entrances and exits Card Access Control via turnstiles to lift lobbies
Fire Protection Addressable fire alarm system
Automatic sprinkler network, wet riser system, hosereels and portable fire extinguishers
Lighting Average 500 lux at desktop level
Incoming Electrical Supply & Electrical Loads Dual feed for 22 kV incoming power supply
Lighting: 20 W/m2
Power: 65 W/m2
Computer Earthing Provision of clean earthing available in each tenant data riser, subject to availability
Standby Generator 20% of estimated tenant normal load
Spare riser For tenants’ inter-floor cabling and specialised services
Total 8 nos risers (4 electrical risers & 4 data risers), subject to availability
Space reserved for tenant’s own generator 12 nos of spare plinths reserved for tenants’ use, subject to availability
Provision of fuel pipe for connection to tenant’s generator system
Telecommunication Fibre Optic and telephone cabling in riser (by Service Provider) and MATV
Lifts 35 Passenger lifts in 5 lift zones with separate car park lifts (3 nos) and service lifts (2 nos)

The above information has been prepared with care. However, it is for guidance purposes only and is subject to change. It cannot form part of an offer or contract. While every reasonable care has been taken in providing this information, Raffles Quay Asset Management Pte Ltd, its subsidiaries, agents or representatives are not responsible for any errors or inaccuracies, or for the consequences of any reliance on such information, whether in the form of costs, claims, expenses, or other losses, and whether direct or indirect.